Megger MIT2500
Catalog #: 1004-745
2.5 kV High Voltage Hand-Held Insulation and Continuity Tester
- Overview
- Specifications
- Summary
- Accessories
Product Highlights
- Insulation testing up to 2.5 kV and 200 GΩ range in a hand held instrument
- Guard terminal for high resistance accuracy
- Adjustable insulation test voltage from 50 V to 2500 V
- Stabilised insulation test voltage
- Rechargeable options for mains and car charging
- Single range, faster continuity testing from 0.01 Ω to 1 MΩ
- Polarisation Index (PI) & Dielectric Absorption Ratio (DAR)
- CAT IV 600 V applications
Each unit Includes
-
- Hard carry case
- Red/Black test lead set with clips
- Red/Blue/Black
- 6 AA (LR6) batteries fitted
- Warranty card
- Owners CD manual
- Quick start guide
- Download Manager software CD
- Factory (non-NIST) Calibration Certificate
| SPECIFICATIONS |
| All quoted accuracies are at +20 °C. |
| Insulation |
| Insulation accuracy |
| 50 Volts |
10 GΩ |
± 2% ± 2 digits ± 4.0% per GΩ |
| 100 Volts |
20 GΩ |
± 2% ± 2 digits ± 2.0% per GΩ |
| 250 Volts |
50 GΩ |
± 2% ± 2 digits ± 0.8% per GΩ |
| 500 Volts |
100 GΩ |
± 2% ± 2 digits ± 0.4% per GΩ |
| 1000 Volts |
200 GΩ |
± 2% ± 2 digits ± 0.2% per GΩ |
| 2500 Volts |
200 GΩ |
± 2% ± 2 digits ± 0.2% per GΩ |
| Service Error BS EN 61557-2 (2007). |
| 50V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.5% |
| 100V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% |
| 250V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% |
| 500V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 10.3% |
| 1000V, ± 2.0% ± 2d, 100kΩ - 900kΩ ± 11.5% |
| Guard terminal performance |
<5% error at 500 kΩ parallel circuit resistance with 100 MΩ load |
| Display range |
Analogue: 1 GΩ full scale |
| Resolution |
0.1 kΩ |
| Short circuit/charge current |
2 mA +0% -50% to EN 61557-2 (2007) (except 2500 V) |
| Terminal voltage accuracy |
-0% +2% ± 2V |
| Test current |
1 mA at min. pass value of insulation to a maximum of 2 mA max |
| Operation |
EN61557 : 0.10 MΩ to 1.0 GΩ |
| Leakage current display |
10% ±3 digits |
| Voltage |
±3% ±2 digits ±0.5% of rated voltage |
| Timer control |
Countdown timer 60 second (adjustable to 10 minutes) |
| Note |
Above specifications only apply when high quality silicone leads are being used. |
| Continuity |
| Continuity measurement |
0.01 Ω to 1 MΩ (0 to 1000 kΩ on analogue scale) |
| Continuity accuracy |
± 3% ± 2 digits (0 to 100 Ω )
± 5% ± 2 digits (100 Ω - 500 k Ω)
Service Error BS EN 61557-4 (2007) -
± 2.0%, 0.1Ω - 2Ω ± 6.8% |
| Open circuit voltage |
5 V ± 1 V |
| Test current |
200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω) |
| Polarity |
Single polarity (Default) / Dual polarity (configurable on setup). |
| Lead resistance |
Null up to 10 Ω |
| Voltage range |
DC: 0 to 600 V
AC: 10 mV to 600 V TRMS sinusoidal (15 Hz to 400 Hz)
Unspecified: 0 – 10 mV (15 to 400 Hz) |
| Volt range accuracy |
DC: ± 2% ± 2 digits
AC: ± 2% ± 2 digits |
| Waveform |
Non-sinusoidal:
± 3% ± 2 digits >100 mV to 600 V TRMS
± 8% ± 2 digits 10 mV to 100 mV TRMS |
| Default voltmeter |
± 0.5% ± 1digit (100 Hz to 400 Hz) unspecified |
| Frequency measurement range |
15 Hz - 400 Hz |
| Frequency measurement accuracy |
± 0.5% ± 1 digits |
| Capacitance measurement |
| Capacitance range |
0.1 nF to 10 µF |
| Accuracy |
± 5.0% ± 2 digits ( 1 nF-10 µF) |
| Results storage |
| Storage capacity |
>1000 test results |
| Data download |
Bluetooth® wireless
Bluetooth® Class II |
| Range |
up to 10 m |
| Power supply |
6 x 1.5 V cells type IEC LR6
(AA, MN1500, HP7, AM3 R6HP) Alkaline
6 x 1.2 NiMH rechargeable cells may be used. |
| Battery life |
3000 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 1000 V into 1 MΩ
Charger (Optional): 12-15 V dc (accessory interface) |
| Dimensions Instrument |
228 mm x 108 mm x 63 mm (9.00 in x 4.25 in x 2.32 in) |
| Weight |
815 g, (1.8 lb) |
| Weight (instrument and case) |
1.75 kg (3.86 lb) |
| Fuse |
Use only 2 x 500 mA (FF) 1000 V 32 x 6 mm ceramic fuse of high breaking capacity
HBC 30 kA minimum. Glass fuses MUST
NOT be fitted |
| Safety protection |
The instruments meet EN 61010-1 (1995) to 600 V phase to earth, Category IV. Refer to safety warnings supplied |
| EMC |
In accordance with IEC 61326 including amendment No.1 |
| Temperature coefficient |
<0,1% per °C up to 1 GΩ
<0,1% per °C per GΩ above 1 GΩ |
| Environmental |
| Operating temperature range |
-10 °C to +55 °C |
| Humidity |
90% RH at 40 °C max |
| Storage temperature range |
-25°C to +70 °C |
| Calibration temperature |
+20 °C |
| Maximum altitude |
2000 m |
| IP rating |
IP 54 |
| Micro / Milli / Meg Ohmmeters/Megohmmeter / Insulation Resistance Testers Template |
| Type |
Battery |
| IR Test Voltage |
1,000 V, 125V, 2,500 V, 250 V, 50 V, 500 V |
| Maximum Insulation Resistance |
200 G Ohms |
| Variable Incremental Voltage |
Yes |
| Display (Megohmmeter) |
Digital |
| Continuity Test |
Yes |
| Live Circuit Voltage Detection |
Yes |
| Automated Test Results |
Dielectric Absorption Ratio, Other |
| Power Supply |
Battery |
| Timer |
Yes |
| CAT Rating |
IV |
| CAT Voltage |
600 V |
| Calibration Included |
Factory Calibration |
| Power Supply Voltage |
120V 50/60 Hz |
| Data Logging |
No |
| IP Rating |
IP54 |
| Battery Type |
AA, NimH |
| Country of Origin |
United Kingdom |
|
Accessories
| Product |
Price |
 |
Megger 1007-157
Catalog #: 1007-157
SP5 Remote Switch Probe CATIV 600V
|
$215.23
|
 |
Megger 1007-160
Catalog #: 1007-160
Carry and Pouch Test
|
$122.23
|
 |
Megger 1007-464
Catalog #: 1007-464
Mains Charger Kit (MIT400/2 series Mk 2)
|
$153.23
|
 |
Megger 1007-637
Catalog #: 1007-637
Replacement lead set 2.50 kV (Red/Black/Blue)
|
$230.23
|
 |
Megger 1007-780
Catalog #: 1007-780
Lead Set Unfused (Red/Black/Green) for MIT481/2 and MIT485/2
|
$230.23
|
 |
Megger 1007-781
Catalog #: 1007-781
Replacement lead set unfused (R/Blk/G)
|
$230.23
|
 |
Megger 1007-887
Catalog #: 1007-887
For MIT400/2 Series Test and Carry Pouch
|
$230.23
|
|
|
|