				Fluke 1625-2 KIT
                
                
                
 			 
				Catalog #: 4325181
Advanced GEO Earth Ground Tester Kit
 
 
                
                    OverviewSpecificationsSummaryCasesCurrent ClampsAccessories 	
                    
				        
                        Product Highlights
    3- and 4-pole Fall of Potential, earth resistance loop testing4-pole Soil Resistivity testingSelective earth ground rod testing using 1 clampStakeless earth ground rod testing using 2 clampsIP56 rated for outdoor useProfessional carrying caseUSB data storage and transfer In addition, the Fluke 1625-2 offers these advanced features: 
    Automatic Frequency Control (AFC) - identifies existing interference and chooses a measurement frequency to minimize its effect, providing more accurate earth ground valueR* measurement - calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to-earth ground would seeAdjustable limits - for quicker testing Each Unit Includes
    Fluke 1625-2 tester2 test leads4 earth ground stakes3 cable reels with wire (2-25 m, 1-50 m)2 clamps (one inducing, one sensing)BatteriesUsers manualC1620 Rugged carrying caseISO 9001 - Statement of Calibration Practices 
                        
    
        
            | Temperature ranges |  
            | Operating temperature range | -10 °C to 50 °C (14° F to 122° F) |  
            | Storage temperature range | -30 °C to 60 °C (-22° F to 140° F) |  
            | Temperature coefficient | ± 0.1 % of range/± 0.1 % of reading/°C <18 °C >28 °C |  
            | Type of protection | IP56 for case, IP40 for battery door according to EN60529 |  
            | Safety | Protection by double and /or reinforced insulation. Max. 50 V to earth per IEC61010-1. 300V CAT II, Pollution degree 2 |  
            | EMC (Emission Immunity) | IEC61326-1: Portable |  
            | Quality standard | Developed, designed and manufactured to comply with DIN ISO 9001 |  
            | External field influence | Complies with DIN 43780 (8/76) |  
            | Auxiliary power | 6 x 1.5 V alkaline (IEC LR6 or type AA ) |  
            | Battery life span | With IEC LR6/type AA: typ. 3,000 measurements (RE +RH ≤ 1 kΩ) |  
            | With IEC LR6/type AA: typ. 6,000 measurements (RE +RH > 10 kΩ) |  
            | Dimensions (WxHxD) | 250 mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in) |  
            | Weight | ≤ 1.1 kg (2.43 lb) without accessories 7.6 kg (16.8 lb) including accessories and batteries in carrying case
 |  
            | Case material | Polyester |    
    
        
            | Measurement of interference voltage dc + ac (UST) |  
            | Measuring Limits of error: method | Fullwave rectification |  
            | Measuring Range | Display Range | Resolution | Frequency Range | Limits of Error |  
            | 1 V to 50 V | 0.0 V to 50 V | 0.1 V | dc/ac 45 Hz to 400 Hz sine | ± (5 % of rdg + 5 digit) |  
            | Measuring sequence | approx. 4 measurements/s |  
            | Internal resistance | approx. 1.5 MΩ |  
            | Max. overload | Urms = 250 V |    
    
        
            | Measurement of interference frequency (F ) |  
            | Measuring Range | Display Range | Resolution | Range | Accuracy |  
            | 6.0 Hz to 400 Hz | 16.0 Hz to 299.9 Hz to 999 Hz | 0.1 Hz to 1 Hz | 1 V to 50 V | ± (1 % of rdg + 2 digit) |    
    
        
            | Earthing resistance (RE) |  
            | Measuring method | Current and voltage measurement with probe as IEC61557-5 |  
            | Open circuit voltage | 20/48 V, ac |  
            | Short circuit current | 250 mA ac |  
            | Measuring frequency | 94, 105, 111, 128 Hz selected manually or automatic. (AFC) 55 Hz in function R* |  
            | Noise rejection | 120 dB (162 / 3 , 50 , 60, 400 Hz) |  
            | Max. overload | Urms = 250 V |    
    
        
            | Electrical measurement specifications |  
            | Intrinsic error or influence quantity | Reference conditions or specified operating range | Designation code | Requirements or test in accordance with the relevant
 parts of IEC 1557
 | Type of test |  
            | Intrinsic error | Reference conditions | A | Part 5, 6.1 | R |  
            | Position | Reference position ± 90° | E1 | Part 1, 4.2 | R |  
            | Supply voltage | At the limits stated by the manufacturer | E2 | Part 1, 4.2, 4.3 | R |  
            | Temperature | 0 °C and 35 °C | E3 | Part 1, 4.2 | T |  
            | Series interference voltage | See 4.2 and 4.3 | E4 | Part 5, 4.2, 4.3 | T |  
            | Resistance of the probes and auxiliary earth electrodes
 | 0 to 100 x RA but ≤ 50 kΩ | E5 | Part 5, 4.3 | T |  
            | System frequency | 099 % to 101 % of the nominal frequency
 | E7 | Part 5, 4.3 | T |  
            | System voltage | 85 % to 110 % of the nominal voltage | E8 | Part 5, 4.3 | T |  
            | Operating error |  | Part 5, 4.3 | R |  
            | Measuring Range | Display Range | Resolution | Accuracy | Operating Error |  
            | 0.020 Ω to 300 kΩ
 | 0.001 Ω to 2.999 Ω | 0.001 Ω | ± ( 2 % of rdg + 2 digit ) | ± ( 5 % of rdg + 5 digit ) |  
            | 3.00 Ω to 29.99 Ω | 0.01 Ω |  
            | 30.0 Ω to 299.9 Ω | 0.1 Ω |  
            | 0.300 kΩ to 2.999 kΩ | 1 Ω |  
            | 3.00 kΩ to 29.99 kΩ | 10 Ω |  
            | 30.0 kΩ to 299.9 kΩ | 100 Ω |    
    
        
            | Measuring time | typ. 8 sec. with a fixed frequency 30 sec. max. with AFC and complete cycle of all measuring frequencies
 |  
            | Measuring error of RH and RS | typ. 10 % of RE + RS + RH |  
            | Max. probe resistance | ≤ 1 MΩ |  
            | Max. auxiliary earth electrode resistance | ≤ 1 MΩ |  
            | Automatic check if error is kept within the limits required by IEC61557-5. If after a measurement of probe-, auxiliary earth electrode- and earthing resistance, a measurement error of higher than 30 % is assumed because of the influencing conditions (see diagram), the display shows a warning symbol "!" and a notice that RS or RH are too high. |    
    
        
            | Automatic switchover of measuring resolution in dependence to auxiliary earth electrode resistance RH |  
            | RH with Umeas = 48 V | RH with Umeas = 20 V | Resolution |  
            | < 300 Ω | < 250 Ω | 1 mΩ |  
            | < 6 kΩ | < 2.5 kΩ | 10 mΩ |  
            | < 60 kΩ | < 25 kΩ | 100 mΩ |  
            | < 600 kΩ | < 250 kΩ | 1 Ω |    
    
        
            | Selective measurement of the earthing resistance |  
            | Measuring method | Current and voltage measurement with probe as per EN61557-5 and current measurement in the individual branch with additional current transformer (patent applied for). |  
            | Open circuit voltage | 20/48 V ac |  
            | Short circuit current | 250 mA ac |  
            | Measuring frequency | 94, 105, 111, 128 Hz selected manually or automatically (AFC), 55 Hz (R*) |  
            | Noise rejection | 120 dB (162 / 3 , 50, 60, 400 Hz) |  
            | Max. overload | Max. Urms = 250 V (measurement will not be started) |    
    
        
            | Measuring Range | Display Range | Resolution | Intrinsic error* | Operating error* |  
            | 0.020 Ω to 30 kΩ | 0.001 to 2.999 Ω | 0.001 Ω | ± (7 % of rdg + 2 digit) | ± (10 % of rdg + 5 digit) |  
            | 3.00 Ω to 29.99 Ω | 0.01 Ω |  
            | 30.0 Ω to 299.9 Ω | 0.1 Ω |  
            | 0.300 kΩ to 2.999 kΩ | 1 Ω |  
            | 3.00 kΩ to 29.99 kΩ | 10 Ω |  
            | * With recommended current clamps/transformers. |  
    
        
            | Type | 3 Pole, 4 Pole |  
            | Display (3 Pole Testers) | Digital |  
            | Ground Resistance Range | 299.9 K Ohms |  
            | Operating Frequency | 55 Hz |  
            | Accuracy | 3-pole and 4-pole Ground Resistance Measurement: ± (2 % rdg + 3 d) |  
            | Measuring Current | 50 mA |  
            | Measuring Voltage | 48 V |  
            | Measuring Frequency | 128 Hz |  
            | Soil Resistivity | Yes |  
            | Display Counts | 2999 |  
            | Stakeless Capability | Yes |  
            | Power Supply | Battery |  
            | CAT Rating | II |  
            | CAT Voltage | 300 V |  
            | Optional Ground Kit Included | Yes |  
            | Auto Ranging | Yes |  
            | Unique Features | • 3- and 4-pole Fall of Potential, earth resistance loop testing
 • 4-pole Soil Resistivity testing
 • Selective earth ground rod
 testing using 1 clamp
 • Stakeless earth ground rod
 testing using 2 clamps
 • IP56 rated for outdoor use
 • Professional carrying case
 • USB data storage and transfer
 • Automatic Frequency Control
 (AFC) - identifies existing
 interference and chooses
 a measurement frequency
 to minimize its effect,
 providing more accurate
 earth ground value
 • R* measurement - calculates
 earth ground impedance at
 55 Hz to more accurately
 reflect the earth ground
 resistance that a fault-toearth
 ground would see
 • Adjustable limits - for
 quicker testing
 |  
            | Warranty | 2 YEARS |  
            | Calibration Included | Factory Calibration |  
            | Power Supply Voltage | Battery Powered |  
            | Data Logging | No |  
            | Interfaces I/O | Other, USB |  
            | IP Rating | IP40, IP56 |  
            | Battery Type | AA |  
            | Product Height | 7.68 IN |  
            | Product Length | 16.14 IN |  
            | Product Width | 20.67 IN |  
            | ECCN Number | EAR99 |  
            | Country of Origin | Romania |  
            | Shipping Height | 7.68 IN |  
            | Shipping Length | 16.14 IN |  
            | Shipping Width | 20.67 IN |  
            | UPC | 095969340335 |  |  
					
                
        
        
              Cases
            
            
                
                        
                            | Product | Price |  
                            |  | Fluke C1620 
                                    Catalog #: 4359042
Professional Earth Ground Instrument Case | $421.24
 
 |  
              Current Clamps
            
            
                
                        
                            | Product | Price |  
                            |  | Fluke EI-1623 
                                    Catalog #: 2577115
Selective/Stakeless Clamp Set for Fluke 1623 | $1,040.24
 
 |  
                            |  | Fluke EI-162AC 
                                    Catalog #: 2577144
Clip-On Current Transformer (Inducing) | $689.24
 
 |  
                            |  | Fluke EI-162X 
                                    Catalog #: 2577132
Clip-On Current Transformer with Shielded Cable Set | $907.24
 
 |  
              Accessories 
				 |  
     |  |