				Extech PQ3450-2-NIST
                
                
                
 			 
				Catalog #: PQ3450-2-NIST
200 A 3-Phase Power Analyzer Kit with 3 - 200A CT Probes, With NIST Calibration
 
 
                
                    OverviewSpecificationsSummaryAccessories 	
                    
				        
                        Product Highlights 
    Kit Supplied with 3 - 200A Current ClampsDatalogging power analyzer - up to 30,000 sets of measurementsLarge dot-matrix, sun-readable, numerical, backlit LCD with easy-to-use onscreen menuFull system analysis with up to 35 parameters:V (phase-to-phase), V (phase-to-ground)A (phase-to-ground)KW / KVA / KVAR / PF (phase)KW / KVA / KVAR / PF (system)KWH / KVAH / KVARH / PFH (system)Phase angleOptional Probe Configurations Available: 1200A Current Clamps or 3000A Flexible Current ProbesAdjustable Current Transformer CT (1 to 600) and Potential Transformer PT (1 to 1000) ratio for high power distribution systemsLog up to 30,000 reading on a removable SD memory card in Microsoft Excel formatWide sampling rate range (2 seconds to 2 hours)Built-in Clock and Calendar Each Unit Includes 
    4 - Voltage Leads With Alligator Clips8 - AA Batteries1 - SD Card1 - 100-240V AC Adapter1 - Case1 - With NIST Calibration 
                          
    
        
            |  | Range | Basic Accuracy |  
            | ACV (True rms) | 600.0V | ±(0.5%rdg+0.5V) |  
            | ACA | 1200A | ±(0.5%rdg+0.5A) |  
            | Active Power (MW) | 9.999MW | ±(1.0%rdg+0.008MW) |  
            | Apparent Power (MVA) | 9.999MVA | ±(1.0%rdg+0.008MVA) |  
            | Reactive Power (MVAR) | 9.999MVAR | ±(1.0%rdg+0.008MVAR) |  
            | Power Factor | 0.00 to 1.00 | ±0.04 |  
            | Frequency Range | 45Hz to 65Hz | ±0.1Hz |  
            | Phase | -180° to +180.0° | ±1° |  
            | Current Clamp input | 200mV, 300mV, 500mV | ±(0.5%rdg+5d) |  
            | 1V, 2V, 3V; user-selectable |  
            | Active Power Energy (MWH) | 0.0kWh to 9.999MWH | ±(2.0%rdg+0.008MWH) |  
            | Apparent Power Energy (MVAH) | 0.0KVAh to 9.999MVAH | ±(2.0%rdg+0.008MVAH) |  
            | Reactive Power Energy (MVARH) | 0.0kVARh to 9.999MVARH | ±(2.0%rdg+0.008MVARH) |  
            | Datalogging | 30,000 readings (2GB SD memory Card) |  
            | CE/CAT rating | CE/CAT III-600V |  
            | Dimensions | 8.86 x 4.92 x 2.52" (225 x 125 x 64mm) |  
            | Weight | Meter: 2.2lbs (1010g) |  
            | General Specifications |  
            | Circuit | Custom single-chip microprocessor LSI circuit |  
            | Display | LCD Size: 81.4 X 61 mm (3.2 X 2.4”) Dot Matrix backlit LCD (320 X 240 pixels)
 |  
            | Measurements | V (voltage phase to phase) V (voltage phase to ground)
 A (Current Phase to ground)
 KW / KVA/ KVAR / PF (Phase)
 KW / KVA/ KVAR / PF (System)
 Power factor
 Phase angle
 Frequency
 |  
            | Wire configurations | 1P/2W, 1P/3W, 3P/3W, 3P/4W |  
            | Voltage ranges | 10 ACV to 600 ACV (Auto Range) |  
            | Current ranges | Current probe input signal voltage (ACV) 200mV(120mV) /2.25V/300mV/500mV/1V/2V/3V
 Current probe input current range (ACA):
 20A/200A/2000A(1200A)/150A/1500A/30A/300A/3000A/60A/600A/6000A
 Note that the meter has universal probe compatibility
 |  
            | Safety standard | IEC1010 CAT III 600 V |  
            | ACV input impedance | 10M ohms |  
            | Range select | ACV | Auto Range |  
            | ACA Manual | Range |  
            | Clamp frequency response | 40 Hz to 1 KHz |  
            | Over-load protection | ACV | 720 ACV RMS |  
            | Over-range | "OL" is displayed; Data on SD card will read ‘9999’ or ‘999’ for over-range data |  
            | Under-range | "UR" is displayed |  
            | Data Hold | Freezes displayed reading |  
            | Data Recording | SD memory card |  
            | SD Card size limits | SD Cards up to 2G; SDHC Cards up to 16G |  
            | Sampling Time | Approx. 1 second (LCD) / 2000 samples per period |  
            | Datalogger | Real time data logger saves data to SD memory card for download to PC (data files open directly to spreadsheet) Sampling rate: From 2 seconds to 7200 seconds (2 hours)
 Max. File capacity: 30,000 records
 |  
            | Data Output | RS232 port |  
            | Operating Temperature | 0 to 50° C (32 to 122°F) |  
            | Operating Relative Humidity | 80% Relative Humidity max. |  
            | Power Supply | Eight (8) ‘AA’ 1.5VDC batteries or AC 9V power adapter |  
            | Meter Power Consumption | 250 mA DC |  
            | Weight | 975g (2.1 lbs.) with batteries |  
            | Dimensions | 225 X 125 X 64 mm (8.86 X 4.92 X 2.52“) |  |  
					
                
        
        
              Accessories
            
            
                
                        
                            | Product | Price |  
                            |  | Extech PQ1000 
                                    Catalog #: PQ1000
Voltage Test Leads Accessory Kit for PQ3350 | $165.21
 
 |  
                            |  | Extech PQ34-12 
                                    Catalog #: PQ34-12
1200A Current Clamp Probes Set of 3 clamp probes w/ 2" | $709.21
 
 |  
                            |  | Extech PQ34-2 
                                    Catalog #: PQ34-2
200A Current Clamp Probes Set of 3 clamp probes w/ 0.8" | $510.21
 
 |  
                            |  | Extech PQ34-30 
                                    Catalog #: PQ34-30
3000A Current Flexible Clamp Probes Set of 3 clamps | $899.21
 
 |  
				 |  
     |  |