				Fluke 6200-2
                
                
                
 			 
            
			
				Portable Appliance Testers
			 
			 
              
            
                
                	
                    
				        
                        Product Highlights
Fluke Simplifies Portable Appliance Testing 
    - Dedicated key for each test for ‘one-touch’ testing
 
     
    - Pre-set pass/fail levels to save time
 
     
    - Large backlit display for easy reading
 
     
    - Single mains socket for appliance connection
 
     
    - Separate IEC socket for easy mains/extension lead testing
 
     
    - Detachable test leads for quick field replacement
 
     
    - Integral carrying handle
 
     
    - USB port for data transfer
 
 
                        Each Unit Includes
    -  Fluke 6200-2 Portable Appliance Tester
 
    - User's manual on CD
 
    - Quick reference guide
 
    - Hard carrying case
 
    - Test lead
 
    - Test probe
 
    - Crocodile clip
 
    - Mains cord
 
    - ISO 9001 - Statement of Calibration Practices 
 
 
                            
                    
                          
    
        
            | Specifications | 
         
        
            | Test specifications | 
            The accuracy specification for the display range is defined as ±(%reading + digit counts) at 23 °C ±5 °C, ≤75% RH. | 
         
        
            | Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C. | 
         
        
            | The measurement range meets the service operating errors specified in EN61557-1: 1997, EN61557-2: 1997, EN61557-4: 1997, EN61557-6: 1997, DIN VDE0404-2. | 
         
        
            | Power-on test | 
            The test indicates reversed L-N, missing PE, and measures the mains voltage and frequency. | 
         
        
            | Display range | 
            90 V to 264 V | 
         
        
            | Accuracy at 50 Hz | 
            ±(2% + 3 counts) | 
         
        
            | Resolution  | 
            1 V | 
         
        
            | Input impedance       | 
            > 1 MΩ // 2.2 nF | 
         
        
            | Maximum input mains voltage | 
            264 V | 
         
        
            | Earth bond test (R pe) | 
            Display Range | 
            0 to 19.99 Ω | 
         
        
            | Accuracy (after bond test zeroing) | 
            ±(2.5% + 4 counts) | 
         
        
            | Resolution | 
            0.01 Ω | 
         
        
            | Test current | 
            200 mA AC -0% +40% into 1.99 Ω 
            25 A AC ±20% into 25 mΩ at 230 V | 
         
        
            | Open circuit voltage | 
            > 4 V AC, < 24 V AC | 
         
        
            | Bond test zeroing | 
            can subtract up to 1.99 Ω | 
         
        
            | Insulation test (R iso) | 
            Display range | 
            0 to 299 MΩ | 
         
        
            | Accuracy | 
            ±(5% + 2 counts) from 0.1 to 300 MΩ | 
         
        
            | Resolution | 
            0.01 MΩ (0 to 19.99 MΩ) 
            0.1 MΩ (20 to 199.9 MΩ) 
            1 MΩ (200 to 299 MΩ) | 
         
        
            | Test voltage | 
            500 V DC -0% + 10% at 500 kΩ load | 
         
        
            | Test current | 
            > 1 mA at 500 kΩ load, < 15 mA at 0 Ω | 
         
        
            | Auto discharge time | 
            < 0.5 s for 1 μF | 
         
        
            | Max. capacitive load | 
            Operational up to 1 μF | 
         
        
            | Touch current test | 
            Display range | 
            0 to 1.99 mA AC | 
         
        
            | Accuracy | 
            ±(4% + 2 counts) | 
         
        
            | Resolution | 
            0.01 mA | 
         
        
            | Internal resistance (via probe) | 
            2 kΩ | 
         
        
            | Measuring method | 
            Probe* | 
         
        
            | Substitute leakage current test | 
            Display range | 
            0 to 19.99 mA AC | 
         
        
            | Accuracy | 
            ±(2.5% + 3 counts) | 
         
        
            | Resolution | 
            0.01 mA | 
         
        
            | Test Voltage | 
            100 V AC ±20% | 
         
        
            | Load/leakage test: load current | 
            Display range | 
            0 A to 13 A | 
         
        
            | Accuracy | 
            ±(4% + 2 counts) | 
         
        
            | Resolution | 
            0.1 A* | 
         
        
            | Load/leakage test: load power | 
            Display range 230 V Mains | 
            0.0 VA to 3.2 kVA | 
         
        
            | Accuracy  | 
            ±(5% + 3 counts) | 
         
        
            | Resolution | 
            1 VA (0 to 999 VA), 0.1 kVA (>1.0 kVA)* | 
         
        
            | Load/leakage test: leakage current | 
            Display range | 
            0 to 19.99 mA | 
         
        
            | Accuracy | 
            ±(4% + 4 counts) | 
         
        
            | Resolution | 
            0.01 mA* | 
         
        
            | PELV test | 
            Accuracy at 50 Hz | 
            ±(2% + 3 counts) | 
         
        
            | Overload protection | 
            300 V rms | 
         
        
            | Warning threshold | 
            25 V rms | 
         
        
            | *The appliance under test is energized at mains potential. | 
         
    
 
  
    
        
            | Environmental specifications | 
         
        
            | Operating temperature | 
            0 to 40 °C | 
         
        
            | Relative humidity | 
            Non condensing <10 °C | 
         
        
            | 95% from 10 to 30 °C | 
         
        
            | 75% from 30 to 40 °C | 
         
    
 
  
    
        
            | Safety specifications | 
         
        
            | Safety rating | 
            Complies with EN61010-1 3rd edition | 
         
        
            | CAT II, 300 V, pol 2 | 
         
    
 
  
    
        
            | Mechanical and general specifications | 
         
        
            | Size (L x W x H) | 
            200 x 275 x 114 mm | 
         
        
            | Weight | 
            3.13 kg | 
         
        
            | Power supply | 
            230 V +10% -15%, 50 Hz ±2 | 
         
        
            | Power consumption (tester) | 
            13 W typical (idle) 
            60 W max. during 25A Bond test | 
         
        
            | Storage | 
            Temperature | 
            -10 to 60 °C | 
         
        
            | Corrosion | 
            70 °C @ 95% RH for 5 days max. | 
         
        
            | Operating altitude | 
            0 up to 2000 m | 
         
        
            | Sealing | 
            IP-40 (enclosure), IP-20 (connectors) | 
         
        
            | EMC | 
            Complies with EN61326-1, portable | 
         
        
            | EMI Immunity | 
            3 V/m | 
         
    
 
                     
                    
                    
                    
                    
                   
                        
              
		 | 
	 
 
				 
				
					
				 
				
					
				 
				
				 
				
			 
		 | 
	 
 
    
     
    
								 | 
							 
						 
					 |