| General Specifications |
| Model |
4620 |
4630 |
| Electrical |
| Ranges (Auto-Ranging 0 to 2000Ω): |
20Ω |
200Ω
|
2000Ω |
| Measurement: |
0.00 to 19.99Ω |
20.0 to 199.9Ω |
200 to 1999Ω |
| Resolution: |
10mΩ |
100mΩ |
1Ω |
| Open Voltage: |
<42V peak |
<42V peak |
<42V peak |
| Resistance Measurement Frequency: |
128Hz square wave |
| Test Current: |
10mA |
1mA |
0.1mA |
| Accuracy: |
±2% of Reading ± 1ct |
±2% of Reading ± 1ct |
±3% of Reading ± 3cts |
Auxiliary Electrode Influence:
Max Res. in Current Circuit
Max Res. in Voltage Circuit |
200Ω
2000Ω |
30kΩ
50kΩ |
50kΩ
50kΩ |
| Interference: |
Rejects high levels of interference voltage (DC, 50 to 60Hz, harmonics):
DC voltage in series with X: 20V; AC voltage in series with Y: 13V peak;
AC voltage in series with Z: 32V peak |
| Response Time: |
Approximately 6 seconds for a stabilized measurement |
| Withstanding Voltage: |
250VAC with spikes of 3000VAC or 1000VDC |
| Power Source: |
(8) C cell batteries;
Alkaline recommended; |
120/230V 50/600Hz
Rechargeable 9.6V, 3.5 Ah NiMH batteries |
| Battery Life: |
1800 15-second measurements; LO BAT indication on LCD |
| Fuse Protection: |
0.1A, 250V, 0.25 x 1.25"; 30kA Interrupt Capacity |
| Mechanical |
| Display: |
31/2 digit, 0.71" (18mm) high; 2000-counts; electroluminescent blue backlight LCD also indicates overrange, test lead shorts and lead reversals |
| Connection: |
Color-coded terminals accept spade lugs with min. gap of 6mm or standard 4mm banana jacks |
| LED Indication: |
Three LEDs indicate high input noise, high auxiliary rod resistance, open leads, blown fuse |
| Operating Temperature: |
14° to 131°F (-10° to 55°C), 20 to 90% RH |
| Storage Temperature: |
-40° to 158°F (-40° to 70°C), 10 to 90% RH with batteries removed |
| Dimensions: |
9.45 x 7.28 x 4.33" (240 x 185 x 110mm) |
| Weight: |
7.75 lbs (3.5kg) |
| Case: |
Heavy duty o-ring sealed field case |
| Mechanical Shock: |
IEC 68-2-27 |
| Vibration Test: |
IEC 68-2-66 |
| Drop Test: |
IEC 68-2-32 |
| Dielectric Test: |
3kV, 50/60Hz, 1 min. between four interconnected measuring terminals and any external metal ground |
| Environmental: |
O-ring sealed against dust and water to IP50 (Protection Index) when case is closed |
| Safety |
| Rating: |
EN 61010-1, Cat. III, Pollution Degree 2, 42V |
| CE Mark: |
Yes |