				AEMC 565
                
                
                
 			 
				Catalog #: 2117.56
Clamp-on Leakage Current Meter (TRMS, 60mA, 600mA, 10A, 100A, 600VAC/DC, Hz, Ohms, Continuity)
 
 
                
                    OverviewSpecificationsSummaryTemp. ProbesAccessories 	
                    
				        
                        Product Highlights 
    Check for leakage and locate insulation breakdowns on live circuits.
Measures leakage current up to 600mA with up to 10μA resolution.
Measures current up to 100Arms
Measures up to 600Vac/dc
Measures Hz on either V or A inputs
Measures Resistance and Continuity
Hold feature freezes Value
Max feature keeps track of highest measured In-rush value
Zero button ideal for measuring relative values
Filter to isolate 50/60Hz fundamental from harmonics
Compatible with VDE 0404
The Model 565 includes two color-coded test leads, soft carrying case and user manual.
 Applications: 
    Ground fault current measurement
Electrical safety compliance testing
Medical device safety testing
Process loop monitoring
General AC load monitoring
Industrial troubleshooting checks 
                          
    
        
            | mA AC Current (TRMS, Auto-Ranging) |  
            | Measurement Range | 0 to 600mA |  
            | Resolution 60mA 600mA
 | 0.01mA (10μA) 0.1mA (100μA)
 |  
            | Accuracy 50 to 60Hz 50 to 500Hz
 500Hz to 3kHz
 | 1.2% of Reading ± 5cts 2.5% of Reading ± 5cts
 3.5% of Reading ± 10cts
 |  
            | AC Current (TRMS, Auto-Ranging) |  
            | Measurement Range | 10 to 100A |  
            | Resolution 10A 100A
 | 0.001A (1mA) 0.01A (10mA)
 |  
            | Accuracy 50 to 60Hz 50 to 500Hz
 500Hz to 3kHz
 | 1.2% of Reading ± 5cts 2.5% of Reading ± 5cts
 3.5% of Reading ± 10cts
 |  
            | AC Voltage (TRMS) |  
            | Measurement Range | 0 to 600V |  
            | Resolution | 0.1V |  
            | Accuracy 50 to 60Hz 50 to 500Hz
 500Hz to 3kHz
 | 1.0% of Reading ± 5cts 1.2% of Reading ± 5cts
 2.5% of Reading ± 10cts
 |  
            | DC Voltage |  
            | Measurement Range | 0 to 600V |  
            | Resolution | 0.1V |  
            | Accuracy | 1.0% of Reading ± 3cts |  
            | Frequency (Auto-Ranging) |  
            | Function | A-Hz | V-Hz |  
            | Resolution 0 to 100Hz 100Hz to 1kHz
 | 0.1Hz | 0.1Hz 1Hz | 1Hz
 |  
            | Sensitivity | 10mArms min | 5Vrms min |  
            | Accuracy | 0.5% of Reading ± 2cts |  
            | Resistance |  
            | Measurement Range | 0 to 1kΩ |  
            | Resolution | 0.1Ω |  
            | Accuracy | 1.0% of Reading ± 3cts |  
            | Continuity |  
            | Measurement Range | 0 to 1kΩ |  
            | Resolution | 0.1Ω |  
            | Buzzer | <35Ω ±25Ω |  
            | Overload Protection | 660Vrms/150Arms |  
            | Nominal Sample Rate | Two measurements per second (approx.) |  
            | MAX Sample Rate | 100ms |  
            | Filter | On (50/60Hz only); Off (Full frequency range) |  
            | In-Rush | Max 100ms sample time |  
            | Power Source | Two 1.5V AAA batteries |  
            | Battery Life | 45 hrs (approx.) |  
            | Power-Off | 10 min approx with user override |  
            | Low Battery Indication | is displayed when battery voltage is low |  
            | MECHANICAL |  
            | Dimensions | 8.5 x 2.5 x 1.18" (218 x 64 x 30mm) |  
            | Jaw Opening | 1.10" (28mm) |  
            | Maximum Conductor Size | 1" (26mm) |  
            | Weight | 10 oz (280g) with batteries |  
            | DISPLAY |  
            | Display Type | Four digit LCD |  
            | Backlight | LED with 180 sec Auto-Off |  
            | ENVIRONMENTAL |  
            | Operating Temperature | 32° to 104°F (0° to 40°C); <80% RH (non-condensing) |  
            | Storage Temperature | 14° to 140°F (-10° to 60°C); <70% RH (non-condensing) |  
            | SAFETY |  
            | Safety Rating | EN 61010-1 Ed. 2001, EN 61010-2-032 Ed. 2003, 600V, Cat. III |  
            | Double Insulation | Yes |  
            | CE Mark | Yes |    
    
        
            | Clamp Meters/Clamp Meters Template |  
            | Type | Current Leakage Clamp |  
            | True RMS | Yes |  
            | Maximum Current AC | 100 A |  
            | Minimum Current AC | 0.01 mA |  
            | Maximum Voltage AC | 600 V |  
            | Minimum Voltage AC | 0.0 mV |  
            | Maximum Voltage DC | 600 V |  
            | Minimum Voltage DC | 0.1 V (100 mV) |  
            | Basic Voltage Accuracy | 2.5% of reading ±5cts |  
            | Digits Display | 3.75 |  
            | Resolution AC Volts | 0.0 V |  
            | Resolution AC Current | 0.01 mA (0.00001 A) |  
            | Maximum Conductor Size | 1.10 IN |  
            | Auto Ranging/Manual | Auto Ranging |  
            | Auto Power Off | Yes |  
            | Detachable Jaw | No |  
            | Rotating Jaw / Swivel | No |  
            | Peak Hold | No |  
            | Min/Max | No |  
            | In-Rush Current | No |  
            | Dual Display | No |  
            | Analog Bargraph on Display | No |  
            | Backlight | Yes |  
            | Remote Display | No |  
            | Resistance | Yes |  
            | Frequency | No |  
            | Continuity | Yes |  
            | Capacitance | No |  
            | Temperature (K T/C) | No |  
            | Temperature (IR Sensor) | No |  
            | Diode Testing | No |  
            | CAT Rating | III |  
            | Overload Protector | Yes |  
            | True Power (KW) | No |  
            | Apparent Power (VA) | No |  
            | Power Factor (PF) | No |  
            | Single Phase/Three Phase | Single Phase |  
            | Crest Factor | No |  
            | Energy (KWh) | No |  
            | Reactive Power (KVAR) | No |  
            | Source/Simulate (Process Clamp) | No |  
         
            | Data Logging | No |  
            | Warranty | 12 MONTHS (1 YEARS) |  
            | Calibration Included | Factory Calibration |  
            | Power Supply Voltage | Battery Powered |  
            | Safety Approval | CE |  
            | Product Weight | 10 OUNCES (0.625 LBS) |  
            | Battery Type | AAA |  
            | Product Height | 1.8 IN |  
            | Product Length | 8.5 IN |  
            | Product Width | 2.5 IN |  
            | Shipping Weight | 3 LBS |  
            | ECCN Number | EAR99 |  
            | HTS/Schedule B Number | 9039310000 |  
            | Country of Origin | Taiwan |  
            | UPC | 685338110166 |  |  
					
				 
					
                
        
        